| VOLT DROP CALCULATIONS | Printable PDF Version | ||
| For information, (extra low voltage dc only) the volt drop on load may be calculated by using the following formula: - | |||
| E=
0.0164 x I x L S |
Where E = Volts drop in volts S = the conductor cross-section area in square millimetres I = the load current in amperes L = the total length, in metres, of conductor from the positive power source Connection to the electrical device and back to the negative source connection. |
||